Unisafe



 

  • Metal-clad air-insulated switchboard
  • Designed for medium voltage distribution
  • Factory-tested for indoor installations
  • Arc-proof switchboards
  • Earthed metallic partitions between compartments
  • Reduction in the use of insulating materials
  • Mechanical safety interlock
  • Compartments made of pre-galvanised sheets
  • Front access of panel for installation, maintenance and routine operations
  • Complete set of apparatus, gas keys and switches, disconnectors, vacuum circuit breakers, contactors
  • Wide range of functional units for any installation requirement
  • Easy-to-assemble modular structure

Product Details

 

Electrical Characteristics of UniSafe Medium Voltage Switchgear

Rated Voltage

KV

12

17.5

24

Power Frequency Test

KV/min

28

38

50

Impules Withstand Voltage

KV

75

95

125

Main Current of Branch Connections

KV

4000

4000

2500

Rated Current of Branch Connections

A

630

630

630

1250

1250

1250

1600

1600

1600

2000

2000

2000

2500

2500

-

3100

3100

-

Rated Short-time Withstand Current

KA/3S

30

40

25

Peak Current

KV

100

100

63

Dimensions of The Panel

Dimensions

width

height

depth

Unit =mm

600-750-1000

1950-2160

1900-2000

Keyword



© 2020. All Rights Reserved. Design and Developed by ariaads.ir